    During a scan operation, the counter tracks signals from internal components such as X, Y, M, S, T, and C. When the count reaches the preset value, the counter contact activates to control the system and perform the required function. A low-speed counter can not only capture switching signals from input terminals (input relays) but also monitor internal component contacts within the PLC.

    Internal counters are categorized based on the frequency of the signals they process, typically divided into low-speed and high-speed counters.

    1) Low-Speed Counter

    There are four main types:

    - 16-bit universal up counter: C0 to C99 (100 points); set value range is K1 to K32767

    - 16-bit power-off keep increment counter: C100 to C199 (100 points); set value range is K1 to K32767

    - 32-bit universal up/down bidirectional counter: C200 to C219 (20 points); set value range is K-2147483648 to +214783648

    - 32-bit power failure keep up/down bidirectional counter: C220 to C234 (15 points); set value range is K-2147483648 to +214783648

    2) High-Speed Counter (C)

    High-speed counters are designed to process external signals received through input terminals, with frequencies reaching several kilohertz. They can also be reset directly via an input terminal.

    The high-speed counter numbers range from C235 to C255, which are all 32-bit up/down bidirectional counters. The counting direction is determined by a special auxiliary relay or an input terminal. The set value range is K-2147483648 to +214783648.

    High-speed counters are generally classified into four categories:

    - 1-phase no start/reset terminal: C235 to C240

    - 1-phase bidirectional: C246 to C250

    - 2-phase A-B phase type: C251 to C255

    The convention between the high-speed counter and the input terminal (input relay) is as follows:

    Note: U = Up counting input; D = Down counting input; A = A phase input; B = B phase input; R = Reset input; S = Start input.

    High-speed counters operate using interrupts, making them independent of the scan cycle. The coil of the selected counter must remain active to ensure the counter and its inputs are continuously operational. No other high-speed processing can use the same input terminals during this time.

    (1) 1-phase high-speed counter C235 to C240

    These counters have a setting range of -2147483648 to +214783648. C241 to C245 include start and reset terminals.

    Description:

    When the count increases and reaches the set value, the contact changes and remains in that state. When counting down, the count resets.

    The counting direction of the 1-phase counter depends on the corresponding flag M8â–¡â–¡â–¡, where â–¡â–¡â–¡ corresponds to the counter number C235 to C245.

    (2) 1-phase bidirectional high-speed counter C246 to C250

    This type of counter has one input for up-counting and another for down-counting. It requires separate inputs for increasing or decreasing rather than relying on special auxiliary relays. Some models also include start and reset inputs.

    (3) 2-phase A-B phase type high-speed counter: C251 to C255

    These counters support two-phase inputs (C251 to C255) and can handle up to two 32-bit binary up/down counters. They operate in interrupt mode regardless of the scan period. These counters also feature application instructions that allow comparison and output operations independently of logical functions. When a counter is selected, the associated start, reset, and input signals become available. The phase relationship between A and B determines whether the counter counts up or down.

    For example, when the A phase signal is ON:

    - If B phase goes OFF → ON: Count up

    - If B phase goes ON → OFF: Count down

    Traffic Signal Lighting

    We started to manufacture traffic signal pole from 2001 and exported from 2002.

    Our firm introduced whole set of good-sized numerical control hydraulic folding equipment(1280/16000) as well as equipped with a series of good-sized professional equipments of armor plate-flatted machine, lengthways cut machine, numerical control cut machine, auto-closed up machine, auto-arc-weld machine, hydraulic redressing straight machine, etc. The firm produces all sorts of conical, pyramidal, cylindrical steel poles with production range of dia 50mm-2250mm, thickness 1mm-25mm, once taking shape 16000mm long, and large-scale steel components. The firm also is equipped with a multicolor-spayed pipelining. At the meantime, for better service to the clients, our firm founded a branch com. The Yixing Jinlei Lighting Installation Com, which offers clients a succession of service from design to manufacture and fixing.

    Traffic Signal Mast,Traffic Signal Light, Camera Pole,Traffic Signal Lighting

    JIANGSU XINJINLEI STEEL INDUSTRY CO.,LTD , https://www.steel-pole.com

    Previous Post: Basic working principle and setting method of gas transformer protection for power transformers - News - Global IC Trade Starts Here Free Join
    Next Post: The living room theater is not a dream? Samsung will push 75-inch curved panel next year
    Home
    Recent Posts
    • Basic working principle and setting method of ga…
    • Basic working principle and setting method of ga…
    • Mitsubishi PLC's internal register Daquan - …
    • The living room theater is not a dream? Samsung …
    • The living room theater is not a dream? Samsung …
    • Serial communication between VB's host compu…
    • DCS system redundancy technology implementation …
    • Serial communication between VB's host compu…
    • DCS system redundancy technology implementation …
    • Deep Neural Network (DNN) = Human cerebral corte…
    • Modbus_Simulator simulation software for small h…
    • Thermocouple's commonly used measuring tempe…
    • Thermocouple's commonly used measuring tempe…
    • Stepper motor reluctance motor static characteri…
    • Stepper motor reluctance motor static characteri…
    • Issues in the selection of DCS - Database & …
    • Issues in the selection of DCS - Database & …
    • Transformer oil quality identification method - …
    • Transformer oil quality identification method - …
    • Causes of fire and explosion in transformers - N…