SF6 Gas Relay Inspection
Cycle | Requirements | |
1) After major maintenance 2) When required |
1) Follow the manufacturer's technical guidelines 2) The set value must meet the operational standards and the response should be accurate. |
SF6 Moisture (Dew Point) Test
Cycle | Requirements | |
1) After major maintenance 2) When needed |
Follow the manufacturer’s technical specifications |
SF6 Gas Leak Test
Cycle | Requirements | |
1) After major maintenance 2) When necessary |
Annual leakage rate ≤1% or as per the manufacturer's instructions |
AC Voltage Withstand Test for Capacitive Voltage Divider of Coupling Capacitor and Capacitive Voltage Transformer
Cycle | Requirements | |
When necessary |
The test voltage should be 75% of the factory test level |
The primary purpose of any fuse cutouts is to provide protection to the lines of your system and the various apparatus on those lines such as transformers and capacitor banks. Fuse cutouts provide reliable protection from low-level overloads that just melt the fuse link, intermediate faults, and very high faults, through maximum interrupting capacity.